潔凈廠房設(shè)計(jì)施工需針對(duì)不同空調(diào)系統(tǒng)有不同設(shè)置
- 發(fā)布人:
- 發(fā)布日期:2017-04-13 17:18:58

1.高級(jí)別潔凈廠房空調(diào)系統(tǒng)宜獨(dú)立設(shè)置。所謂高級(jí)別潔凈廠房是指千級(jí)以上潔凈廠房,其原因是高級(jí)別潔凈廠房空調(diào)送風(fēng)量大,如同樣面積的潔凈廠房,百級(jí)潔凈廠房的空調(diào)風(fēng)量是十萬級(jí)的3.4倍,是萬級(jí)的2.25倍。另外高級(jí)別潔凈廠房的使用頻率遠(yuǎn)低于低級(jí)別手術(shù)室,這樣無論是一個(gè)空調(diào)系統(tǒng)負(fù)擔(dān)多個(gè)高級(jí)別潔凈廠房,或是一個(gè)空調(diào)系統(tǒng)負(fù)擔(dān)一個(gè)高級(jí)別潔凈廠房和多個(gè)低級(jí)別潔凈廠房,都會(huì)使空調(diào)系統(tǒng)長時(shí)間處于"大馬拉小車"的運(yùn)行狀態(tài)。例如一個(gè)空調(diào)系統(tǒng)負(fù)擔(dān)1間百級(jí)潔凈廠房和2間萬級(jí)手術(shù)室或4間十萬級(jí)潔凈廠房,只要高級(jí)別潔凈廠房不使用,則潔凈廠房設(shè)計(jì)施工系統(tǒng)設(shè)計(jì)風(fēng)量至少大于此時(shí)所需風(fēng)量的112%和84%,亦即此時(shí)系統(tǒng)所需風(fēng)量僅為系統(tǒng)設(shè)計(jì)風(fēng)量的47%和54.3%,而且此種因潔凈廠房使用與否引起的風(fēng)量變化,不宜采用變頻調(diào)速方式進(jìn)行調(diào)節(jié),只能用調(diào)節(jié)總風(fēng)閥的方式調(diào)節(jié)風(fēng)量以適應(yīng)系統(tǒng)風(fēng)量變化,然而此種方式顯然不節(jié)能。所以無論從節(jié)約能源的角度,或是從使用可靠性、靈活性的角度,高級(jí)別潔凈廠房都應(yīng)"按間"獨(dú)立設(shè)置空調(diào)系統(tǒng),即一個(gè)凈化空調(diào)系統(tǒng)對(duì)應(yīng)一間潔凈廠房。
1 high level clean room air-conditioning system should be independent set. The so-called high-level clean plant is a thousand or more clean plant, the reason is the high level of air conditioning air supply, as the sample size of the clean room, clean room air conditioning air is 3.4 times one hundred thousand times, is 2.25 times. In addition to the use of high levels of clean plant frequency is far lower than the low level operation room, so whether it is a burden on a large air-conditioning system to clean the plant, or a high level of air conditioning system to burden a high level of clean plant and a number of low-level clean plant, will make the air conditioning system long time in the running state of the big horse car. Such as an air conditioning system burden of 1 hundred grade clean workshop and 2 or one hundred thousand grade clean workshop, as long as the high level of clean plant is not used, the design and construction system design and construction system is at least 112% and 84%, which means the system is designed for the system design of 47% and 54.3%, and this is due to the use of variable frequency speed adjustment, adjustment of the total air valve to adjust the air volume to adapt to the system, but this way is not energy. Therefore, whether from the perspective of energy conservation, or from the use of reliability, flexibility, the high level of clean plant should be "according to the" independent air-conditioning system, that is, a clean air-conditioning system corresponding to a clean plant.
2.對(duì)于低級(jí)別潔凈廠房,盡管與高級(jí)別潔凈廠房相比空調(diào)風(fēng)量小的多,但一個(gè)空調(diào)系統(tǒng)所負(fù)擔(dān)的潔凈廠房間數(shù)也不宜過多,因?yàn)闈崈魪S房的使用情況具備不確定性。愈是高等級(jí)廠家,潔凈廠房為滿足特殊繁忙情況,設(shè)置愈多。手術(shù)室多,正常情況下的同時(shí)使用系數(shù)低,這樣當(dāng)一個(gè)空調(diào)系統(tǒng)所負(fù)擔(dān)的潔凈廠房間數(shù)較多時(shí),系統(tǒng)常處于"供大于求"的狀態(tài),其運(yùn)行能耗勢(shì)必較高,就象有的廠家所反映的"建的起,用不起"。對(duì)于低級(jí)別潔凈廠房一個(gè)空調(diào)系統(tǒng)所負(fù)擔(dān)的潔凈廠房不宜多于四至五間,而且一個(gè)系統(tǒng)負(fù)擔(dān)潔凈廠房過多,也會(huì)造成使用上的不可靠。
2 for the low level of clean plant, despite the high level of clean room air conditioning air is much smaller, but an air conditioning system, the burden of the clean room number also should not be too much, because the use of clean plant with uncertainty. The more high grade manufacturers, clean workshop to meet the special busy, set the. Operation room, normal circumstances, while the use of low coefficient, so that when a large number of air-conditioning system burden of a large number of clean room, the system is often in a state of oversupply, the energy consumption will be higher, as some manufacturers reflect the construction of the up, can not afford". For low level cleanroom air conditioning system of the burden of clean plant should not be more than four to five, and a burden on the system clean workshop too much, caused by the use of unreliable.
3.中央清潔大廳、清潔走廊、高級(jí)別手術(shù)間的準(zhǔn)備區(qū)、無菌室等應(yīng)由一個(gè)單獨(dú)的空調(diào)系統(tǒng)負(fù)擔(dān),目的是保證潔凈廠房外部空氣環(huán)境時(shí)時(shí)處于"臨戰(zhàn)"狀態(tài),那種將以上部位空調(diào)合在低級(jí)別潔凈廠房空調(diào)系統(tǒng)中的做法
. central clean hall, corridor in the clean and high level operation between the preparation zone, sterile rooms should be a separate air conditioning system burden, the purpose of which is to ensure clean workshop outside air environment are always in the "battle" state, that will be part of the air conditioner in the low-level clean factory building air conditioning system
顯然不合理。因?yàn)楹显谝黄鸬目照{(diào)系統(tǒng),或是在潔凈廠房停止使用時(shí)系統(tǒng)送風(fēng)能耗過大,或是無法保證潔凈廠房設(shè)計(jì)施工外部氣候環(huán)境處于受控狀態(tài)。
Obviously unreasonable. Because of the air conditioning system, or in the clean plant to stop using the system to send wind energy consumption is too large, or can not guarantee the clean plant design and construction of the external climate environment in a controlled state.
潔凈廠房空調(diào)風(fēng)系統(tǒng)的劃分原則應(yīng)該是運(yùn)行可靠、調(diào)節(jié)靈活、各司其責(zé)、節(jié)約能源。在潔凈廠房設(shè)計(jì)施工 http://www.jnjkjh.com/ 方面,巨康是專業(yè)的,行業(yè)內(nèi)領(lǐng)軍品牌,值得您的信賴!
The principle of division of clean workshop air conditioning system should be reliable operation, flexible adjustment, each department is responsible for energy conservation. In the design and construction of clean plant, more and more professional, industry leading brands, worthy of your trust!